Skip to content

Ventilation Rates

Standard Airtightness Method

Where neither a measured air permeability or design air change rate is known, the whole-building air permeability is assumed based on BS 12831 Table B.6 default values.

Property typeAir Permeability @ 50 Pa (m³/h.m²)
All properties12

NOTE

Refer to BS EN 12831-1:2017 for more information.

Ventilation Systems

Where a mechanical ventilation system exists, the supply and extract ventilation rate will vary based on the type of system.

The supply air temperature will be the design external air temperature in all cases except MVHR, where the heat recovery percentage will be applied relative to the extract air temperature.

The data is derived from Standard Assessment Procedure (10.2) Section 2.6.1 and converted to a airflow volume based on the total internal air volume of the ventilation zone.

Ventilation SystemSupply Flow RateExtract Flow Rate
Mechanical Ventilation (MV)0.5 ACH0.5 ACH
Mechanical Extract Ventilation (MEV)-0.5 ACH
Mechanical Ventilation with Heat Recovery (MVHR)0.5 ACH0.5 ACH
Positive Input Ventilation (PIV)20 m³/h-

NOTE

Refer to Standard Assessment Procedure (10.2) for more information.

Minimum Room Air Change Rates

For each heated room, the default minimum air change rate (ACH) used is determined by the room type (habitable vs non-habitable).

Additionally, ANY room that has no external envelope area (e.g. fully enclosed rooms such as landings) will use a zero minimum air change rate.

This data is derived from CIBSE Domestic Heating Design Guide (2026) Table 2-18.

Room TypeMinimum ACH (1/h)
Bathroom0.5
Bedroom0.5
Bedroom with en-suite0.5
Bedroom/study0.5
Breakfast room0.5
Cloakroom/WC0.5
Dining room0.5
Dressing room0.5
Family/breakfast room0.5
Games room0.5
Hall0.5
Internal room/corridor0.0
Kitchen0.5
Landing0.5
Lounge/sitting room0.5
Living room0.5
Shower room0.5
Store room0.5
Study0.5
Toilet0.5
Utility room0.5

NOTE

Refer to CIBSE Domestic Heating Design Guide (2026) for more information.

Infiltration Rates of Ventilation Devices

When unknown, the infiltration rate of ventilation devices will be determined by the device type based on the table below. This data is sourced from Standard Assessment Procedure (10.2) Table 2.1.

Ventilation devices that are classified as an Air Terminal Device (ATD) according to the BS 12831 definition will increase the infiltration rate of the room that the device exists in.

Ventilation Device TypeInfiltration Rate (m³/h)Air Terminal Device
Chimney or flue (closed fire)10No
Chimney or flue (solid fuel burner)20No
Chimney or flue (other heater)35No
Chimney (open)80No
Chimney (blocked)20No
Flueless gas fire40Yes
Intermittent extract fan10No
Other open flue (vertical duct)20No
Passive vent10Yes

NOTE

Refer to Standard Assessment Procedure (10.2) for more information.